Corrected from:
Behavior of the new version:
The call of an OPC UA Server method by a Client works correctly.
Description of the behavior:The call of an OPC UA Server method by a Client results in a "BadNoEntryExists" error status code.
Conditions under which the behavior occurs
- In the PLC-Designer - Mapping Editor a predefined OPC UA user model with a method is imported.
- The method is mapped to a matching method function block in the PLC application.
- The PLC Designer project is downloaded to the Controller.
- A Client is connected to the Controller OPC UA Server with the loaded user model.
Affected products:
Short-term measure, recommendations, evaluation:
Delete the method in the imported user model and create a new one with the PLC Designer - Mapping Editor.