Fixed as of:
No direct fix is provided in the i950 firmware.
An improvement to the EtherCAT master is required. It must repeatedly poll the slaves until they can be initialized. This will be incorporated into a future controller firmware release as part of the continuous product improvement process.
Behavior of the new version:
With an i950A running firmware version V01.05.x or V01.10.00, this behavior does not occur, for example.
Description of the behavior:
When starting up the CbM topology consisting of a Lenze C5x0 controller and an i950, the i950 EtherCAT slave is not recognized as “connected.” The log contains a message such as“ECAT cable not connected.” If the i950 is powered on slightly earlier, this behavior is not observed.
Conditions under which the behavior occurs:
In general, this can occur whenever the controller boots up faster than the drive/slave.
At the time the EtherCAT slave scan was performed, the i950 slave was not yet available. TheEtherCAT master then does not check again.
Affected products:
This behavior was observed with an i950A running firmware version V01.14.1.
In principle, however, it can also occur in other configurations, including with different versions or other slaves.
Short-term measures, recommendations, assessment:
The EtherCAT master or the PLC must be restarted after the slave has fully started up.
[Automatic Translation]